EtherCAT bus coupler XB-EC-12 ctrlX I/O - R911406090
EtherCAT bus coupler XB-EC-12 ctrlX I/O - R911406090
Regular price
€214,00 EUR
Regular price
Sale price
€214,00 EUR
Unit price
/
per
Auf Lager - Lieferzeit 2-5 Werktage*
The XB-EC-12 bus coupler is the link between an EtherCAT network and the ctrlX I/O system. The bus coupler supplies the connected I/O modules with the logic voltage UL and the peripheral voltage UP .
The corresponding ESI files are available for integration into the higher-level system. You can find the ESI files here .
Technical data
Technical data
General technical data:
- Connection technology: Push-in terminal
- Nominal voltage (UL, UP): DC 24 V (19.2 V to 30 V, including tolerance and residual ripple) PELV/SELV (safety extra-low voltage)
- Current consumption UL at nominal voltage 24 V: Max. 60 mA (without I/O modules), max. 3 A (entire system with I/O modules)
- Current consumption UP at nominal voltage 24 V: Typ. 7 mA (without I/O modules, max. 8 A (entire system with I/O modules)
- Power consumption UL at nominal voltage 24 V: Max. 1.44 W (without I/O modules), max. 72 W (total system with I/O modules)
- Power consumption UP at nominal voltage 24 V: Typ. 0.17 W (without I/O modules), max. 192 W (total system with I/O modules)
- Maximum power consumption of the module: 2.64 W
- Protection (UL): Internally with a fuse
- Protection (UP): No internal protection. Protection against overload must be provided by the operator through an external fuse.
- Reverse polarity protection (UL, UP): Available
- Overvoltage protection UL and UP: Present, in case of overvoltage the fuses can blow.
- Transient protection UL and UP: Available, suppressor diodes, pulse load up to 1500 W
- Voltage dips at power supply interfaces: PS1 <1 ms, evaluation criterion A
- Maximum number of modules per station: 30 without UL replenishment
- Width of process data: 10 bytes
- Configuration: No address or configuration setting required
- Dimensions: 23.3 mm × 105 mm × 99 mm (width × height × depth)
- Weight: 115 g (module including plug)
- Potential isolation: DC 1211 V DC UP to UL, DC 707 V DC UP/UL to FE (not evaluated by UL)
- EMC immunity: According to EN 61000-6-2 and EN 61000-6-4
- Installation position: Vertical, on a horizontal support
rail - Marking, approvals: CE, UKCA, UL