Bosch Rexroth
Digital input module XI180202 ctrlX I/O 2-channel (24 VDC, 1 µs filter time, 2-wire, timestamping) - R911421643
Digital input module XI180202 ctrlX I/O 2-channel (24 VDC, 1 µs filter time, 2-wire, timestamping) - R911421643
Couldn't load pickup availability
The XI180202 digital input module is used to acquire binary 24 V control signals and their timestamps in a ctrlX I/O station. The module features two channels and a two-wire interface. The signal status is indicated by the channel LED on the detachable peripheral connector. The signals are pre-processed with a 1 μs filter and timestamped to indicate the edge transition time. The timestamps are based on distributed system time (DC).
The logic and peripheral power supply as well as the EtherCAT-based module communication are forwarded through the module.
The corresponding ESI files are available for integration into the higher-level system.
Technical data
Technical data
General technical data
- Number of entrances: 2
- Connection type: Push-in terminal
- Connection technology: 2-wire technology
- Specification: EN 61131-2, Type 1/3
- Input filter: 1 μs
- Signal voltage "0": -3 V to 5 V
- Signal voltage "1": 11 V to 30 V
- Input current: Typically 2.4 mA per channel
- Reverse polarity protection of the inputs: Reverse polarity protected up to 30 V
- Accuracy of timestamps without input filter time and accuracy of DC clock: 10 ns
- DC clock accuracy: <1 μs
- Max. output current per terminal UOUT 24 V: 1 A
- Max. total current UOUT 24 V: 1 A
- Nominal voltage (UL/UP): DC 24 V (19.2 V to 30 V, including tolerance and ripple) PELV/SELV (Safety Extra Low Voltage)
- Current consumption UL: 30 mA
- Current consumption UP: 20 mA + load UOUT
- Maximum power consumption of the module: 1.35 W
- Data width in the process image: 34 bytes
- Configuration: No address or configuration setting required
- Dimensions: 12 mm × 105 mm × 99 mm (width × height × depth)
- Weight: 85 g (module including connector)
- Potential isolation: DC 1200 V UP to UL, DC 707 V UP/UL to FE, tested for 60 s each (not evaluated by UL)
- EMC resistance: According to EN 61000-6-2 and EN 61000-6-4
- Installation position: Vertical, on a horizontal support rail
- Markings, approvals: CE, UKCA, UL
Downloads
Downloads
Share
*Applies to deliveries to Germany. Delivery times for other countries and information on calculating the delivery date can be found here .
View full details