The XI112108 digital input/output module is used to acquire and output binary 24V control signals in a ctrlX I/O station. The module features 8 input and 8 output channels, each implemented in single-wire configuration. The signal status is indicated by the channel LED on the detachable peripheral connector. The digital outputs are powered from the peripheral supply voltage UP.

The logic and peripheral power supply as well as the EtherCAT-based module communication are forwarded through the module.

The corresponding ESI files are available for integration into the higher-level system.

Technical data

General technical data

  • Number of entrances: 8
  • Number of outputs: 8
  • Connection type: Push-in terminal
  • Connection technology: 1-wire technology
  • Nominal voltage (UL/UP): DC 24 V (19.2 V to 30 V, inclusive)
    Tolerance and residual ripple) PELV/SELV (Safety Extra Low Voltage)
  • Current consumption UL: 30 mA
  • Current consumption UP: 48 mA + load
  • Maximum power consumption of the module: 1.8 W
  • Bit width in the process image: 1 byte input, 1 byte output
  • Configuration: No address or configuration setting required
  • Dimensions: 12 mm × 105 mm × 99 mm (width × height × depth)
  • Weight: 100 g (module including connector)
  • Potential isolation: 1211 V DC UP to UL, 707 V DC UP/UL to FE (not evaluated by UL)
  • EMC resistance: According to EN 61000-6-2 and EN 61000-6-4
  • Installation position: Vertical, on a horizontal support rail
  • Markings, approvals: CE, UKCA, UL
Digital inputs
  • Specification: EN 61131-2, Type 1/3
  • Input filter: 3 ms
  • Signal voltage "0": -3 V ... 5 V
  • Signal voltage "1": 11 V ... 30 V
  • Input current: Typically 2.4 mA

Digital outputs
  • Maximum output current: 0.5 A per channel
  • Total current of the channels: max. 4 A
  • Rated load: Resistive, maximum 12 W (48 Ω; at rated voltage)
  • Minimum load: 10 kΩ
  • Rise time (TRise): No load: 8.3 µs at digital input, 8.5 µs at 240 Ω, 100 mA; Resistive load: 10 µs at 48 Ω, 500 mA
  • Drop-out time (TFALL): No load: On digital input 1.4 ms 50 µs at 240 Ω, 100 mA, Resistive load: 11 µs at 48 Ω, 500 mA
  • Inductive shutdown energy: Maximum 150 mJ per channel
  • Overload behavior: Granular channel shutdown with automatic restart
  • Backfeed resistance: Not backfeed resistant, external precautions necessary