Bosch Rexroth
Digital output module XI211208 ctrlX I/O 8-channel (24 VDC, 0.5 A), 2-wire, PNP - R911406101
Digital output module XI211208 ctrlX I/O 8-channel (24 VDC, 0.5 A), 2-wire, PNP - R911406101
Couldn't load pickup availability
The digital output terminal XI211208 is used to output binary 24 V control signals in a ctrlX I/O station. The terminal is designed with 8 channels in 2-wire technology. The signal status is displayed on the channel LED on the removable peripheral connector. The digital outputs are supplied from the peripheral supply voltage U P. The logic and peripheral supply as well as the Ethercat-based module communication are routed through the module.
The corresponding ESI files are available for integration into the higher-level system. You can find the ESI files here .
Technical data
Technical data
General technical data:
- Number of outputs: 8
- Connection type: push-in terminal
- Connection technology: 2-wire technology
- Maximum output current: 0.5 A per channel. The GND contact assigned to the channel must not be loaded beyond the maximum output current of 0.5 A.
- Total current of the channels: max. 4 A
- Nominal load: Ohmic, maximum 12 W (48 Ω; at nominal voltage)
- Minimum load: 10 kΩ
- Rise time (TRise): No load: On digital input 8.3 µs, 8.5 µs at 240 Ω, 100 mA, Resistive nominal load: 10 µs at 48 Ω, 500 mA
- Fall time (TFALL): Without load: On digital input 1.4 ms, 50 µs at 240 Ω, 100 mA, Resistive nominal load: 11 µs at 48 Ω, 500 mA
- Inductive shutdown energy: Maximum 150 mJ per channel
- Behavior in case of overload: Channel-granular shutdown with automatic restart
- Regeneration protection: Not regeneration proof, external precautions necessary
- Nominal voltage (UL/UP): DC 24 V (19.2 V to 30 V, including tolerance and residual ripple) PELV/SELV (safety extra-low voltage)
- Current consumption UL: 35 mA
- Current consumption UP: 15 mA + load
- Maximum power consumption of the module: 2.06 W
- Bit width in the process image: 1 byte (8 bits)
- Configuration: No address or configuration setting required
- Dimensions: 12 mm × 105 mm × 99 mm (width × height × depth)
- Weight: 100 g (module including plug)
- Potential isolation: 1211 V DC UP to UL, 707 V DC UP/UL to FE (not evaluated by UL)
- EMC immunity: According to EN 61000-6-2 and EN 61000-6-4
- Installation position: Vertical, on a horizontal mounting rail
- Marking, approvals: CE, UKCA, UL (⮫ File No. E210730)
Downloads
Downloads
Share
*Applies to deliveries to Germany. Delivery times for other countries and information on calculating the delivery date can be found here .
View full details